You are viewing the site in Italian, other language is available.

View in

Brass Threaded Solenoid Valve for Gas

Normally closed with manual reset under voltage, max. pressure 500 mbar

VERSION WITH MAXIMUM PRESSURE 6 BAR, ON REQUEST

sku model price info add to cart

00000060520

BRASS THREADED SOLENOID VALVE FOR GAS - 1/2" FF - 500 mbar

173,60 Excl. Taxes

Physical data

UM Base:
NR

Dimension:
19 × 9 × 14 cm

Volume:
0.0025 m3

Weight:
0,85 kg

Minimum Order Quantity:
1

Customs data

Customs Code
84169000

Buy
Info Request

00000060521

BRASS THREADED SOLENOID VALVE FOR GAS - 3/4" FF - 500 mbar

173,60 Excl. Taxes

Physical data

UM Base:
NR

Dimension:
N/A

Volume:
0 m3

Weight:
0,00 kg

Minimum Order Quantity:
1

Customs data

Customs Code
84169000

Buy
Info Request

00000060522

BRASS THREADED SOLENOID VALVE FOR GAS - 1" FF - 500 mbar

196,15 Excl. Taxes

Physical data

UM Base:
NR

Dimension:
18 × 11 × 15 cm

Volume:
0.003 m3

Weight:
1,15 kg

Minimum Order Quantity:
1

Customs data

Customs Code
84169000

Buy
Info Request

Product informations

Normally closed solenoid valve for gas for gas with manual reset under voltage; it can be reset only in the presence of mains voltage and only when the gas detector does not give any danger signals.

NB. the valve will not open by simply powering the coil, you must manually press the reset mechanism.

Technical Features

USE not aggressive gases of the three families (dry gases)
ROOM TEMPERATURE - 20°C ÷ + 60°C
SUPPLY VOLTAGES 230 V 50 - 60 Hz (only single-phase, the device does not work if powered with three-phase voltage)
ELECTRICAL WIRING electric cable (length 3 m, with wire terminals)
ABSORBED POWER 230 V = 9 VA
MAXIMUM WORKING PRESSURE 500 mbar
CLOSING TIME < 1 s
DEGREE OF PROTECTION IP65 (protected against jets of water pumped from any direction and completely hermetic against dust and fumes)
COIL PROTECTION II 3G Ex mc ec nC IIC T4 Gc X - II 3D Ex mc tc IIIC T135°C Dc X - suitable for explosive atmospheres
CLASSE A
MATERIALS brass body
MECHANICAL STRENGTH group 2
CONNECTIONS 1/2" FF - 3/4" FF - 1" FF
COMPLIANCE
  • Regulation (EU) 2016/426 (appliances that burn gaseous fuels)
  • EN 60079-0-7-14-15-18-31 - ATEX Directive 2014/34/EU
  • EMC Directive 2014/30/EU
  • LVD Directive 2014/35/EU
  • RoHS II Directive 2011/65/EU